ПРОДУКТИ
Код за електронния магазин
Парола
Welcome to Cairox Bulgaria

RWR-N (RAL9016) • Circular swirl diffusers with fixed blades

  • Swirl diffusers
  • Circular
  • Steel
  • White, RAL 9016
  • Fixed blades

Circular swirl ceiling diffusers with fixed blades

Brand

  • Cairox

Application

  • For air supply and exhaust in ventilation and air conditioning systems.

Material

  • Steel

Colour

  • Standard colour white, RAL 9016
  • Other colours available upon request

Composition

  • Fixed blades

Mounting

  • Fixing with central screw into the crossbar of the plenum box

Accessories

  • Plenum box, type RER-LB
  • Insulated plenum box, type RER-LB ISO
  • Regulating valve for plenum box, type CRC
  • Mounting crossbar for direct duct mounting, type FGN
  • Mounting crossbar for direct ceiling mounting, type FHN

Text for tender

Копирай
  • The air supply diffusers are of the swirl type with fixed blades. They are made of steel with white powder coating RAL 9016 and supplied with a volume control damper in the plenum box.
  • Cairox type RWR-N+RER-L

Order example

  • RWR-N, 315 + RER-LB + CRC 250

Explanation

RWR-N = Diffuser type

315 = Diffuser size (Ø diffuser neck connection)

Accessories

RER-LB = Plenum box

CRC = Regulating valve for plenum box
250 = Plenum box connection diameter

Dimensions

Модел

ØA [mm]

ØN1 [mm]

ØN [mm]

125

173

123

125

160

208

158

160

200

272

198

200

250

328

248

250

315

403

313

315

355

501

353

355

400

501

398

400

500

594

498

500

Selection

QvRWR-N125160200250315355400500
Aeff0.010.010.020.020.030.040.050.06
40Lth0.40
Ps7
Veff1.10
Lw<20
60Lth0.600.50
Ps167
Veff1.701.40
Lw22<20
80Lth0.800.70
Ps2912
Veff2.201.80
Lw3021
100Lth10.90.80
Ps45186
Veff2.802.301.60
Lw3627<20
120Lth1.201.100.90
Ps64269
Veff3.402.701.90
Lw4133<20
150Lth1.501.801.101
Ps10173145
Veff4.204.552.401.80
Lw474725<20
200Lth22.301.501.30
Ps179113249
Veff5.605.603.202.50
Lw55533323
250Lth 1.901.701.40
Ps 38144
Veff 3.903.102.10
Lw 3930<20
300Lth 2.3021.701.80
Ps 552064
Veff 4.703.702.502.30
Lw 4435<20<20
400Lth 32.702.202.40
Ps 9836118
Veff 6.304.903.403.10
Lw 52432825
500Lth 3.302.8032.50
Ps 5618126
Veff 6.104.203.902.80
Lw 493431<20
600Lth 43.303.603
Ps 8026189
Veff 7.405.104.603.30
Lw 54393523
700Lth 3.904.203.502.70
Ps 3524138
Veff 5.905.403.903.10
Lw 444028<20
850Lth 4.7054.303.30
Ps 52361912
Veff 7.206.604.703.80
Lw 49463325
1000Lth 5.505.9053.90
Ps 72502617
Veff 8.407.705.604.50
Lw 54503829
1200Lth 64.70
Ps 3724
Veff 6.705.40
Lw 4334
1400Lth 75.50
Ps 5033
Veff 7.806.30
Lw 4739

Symbols and specifications

  • Q = Air volume in m³/h
  • Ak = Effective surface (free area) in m²
  • B = Distance between the diffusers in m
  • H = Installation height of the diffusers in m
  • Vz = Maximum velocity at the occupied zone according to distance between the diffusers and installation height in m/s
  • Vk = Average effective velocity through the diffuser in m/s
  • X0.25 = Throw length in m at an end velocity Vt of 0,25m/s
  • Ps = Static pressure loss given in Pa
  • Lw(A) = Acoustic power in dB(A)


  • The throw X0.25 is given at an end velocity of 0.25m/s for a smooth ceiling without any obstacles.
  • The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by dividing the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.
  • In order to achieve a high comfort level, selections can be made according to the maximal velocity at the occupied zone Vz. These values are given at distances between diffusers B and installation heights H. Velocities Vz lower than, or equal to 0,25m/s at the occupied zone are advised.
  • The pressure losses Ps are given for diffusers without damper of with fully opened damper.
  • The acoustic power values Lw(A) are given for diffusers without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
  • For all special requirements, please contact our engineering office.

Placement instruction

CopyrightEthics policyDisclaimerDuct calculator