RWR-2 (RAL9016) • Circular swirl diffusers with fixed blades

  • Swirl diffusers
  • Circular
  • Steel
  • White, RAL 9016
  • Fixed blades

Circular swirl ceiling diffusers with flat frame and fixed blades

Brand

  • Cairox

Application

  • For air supply and exhaust in ventilation and air conditioning systems.

Material

  • Steel

Colour

  • Standard colour white, RAL 9016
  • Other colours available upon request

Composition

  • Fixed blades

Mounting

  • Fixing directly on the collar
  • Fixing with central screw
  • For the mounting of RER-LB and RER-LB ISO, the airtight connection between the diffuser and the plenum box is made halfway the upright collar of the diffuser. This is why the plenum box has to be installed at the right height before mounting the finishing grille.

Accessories

  • Plenum box, type RER-LB
  • Insulated plenum box, type RER-LB ISO
  • Regulating valve for plenum box, type CRC
  • Mounting crossbar for direct duct mounting, type FGN
  • Mounting crossbar for direct ceiling mounting, type FHN

Text for tender

Копирай
  • The air supply diffusers are of the swirl type with a flat frame. They are made of steel with white powder coating RAL 9016 and supplied with a plenum box.
  • Cairox type RWR-2+RER-L

Other available products

  • Square type VWR-2 available upon request

Order example

  • RWR-2, 200 + RER-LB + CRC 250

Explanation

RWR-2 = Diffuser type

200 = Neck size of diffuser

Accessories

RER-LB = Plenum box

CRC = Regulating valve for plenum box
250 = Plenum box connection diameter 250

Selection

RWR-2100125160200250315355
QAk0.00560.00860.01410.02240.03450.05370.0676
B1.22.43.61.22.43.61.22.43.61.22.43.61.22.43.61.22.43.61.22.43.6
40 H=2.70.510.250.150.280.130.07               
VzH=3.20.280.160.10.140.080.05               
 H=3.80.160.10.070.080.050.03               
Vk21.3     
X0,252.11.6     
Ps2410     
Lw(A)25<20     
60 H=2.70.770.380.220.40.180.10.310.140.08            
VzH=3.20.420.240.160.210.110.070.160.090.05            
 H=3.80.240.160.110.110.070.050.090.050.04            
Vk31.91.2    
X0,252.61.81.7    
Ps54216    
Lw(A)3822<20    
100 H=2.7   0.680.310.170.520.240.130.390.170.09         
VzH=3.2   0.350.190.120.260.140.090.190.10.06         
 H=3.8   0.190.120.080.140.090.060.10.060.04         
Vk 3.221.2   
X0,25 2.321.8   
Ps 59175   
Lw(A) 3830<20   
150 H=2.7      0.780.350.20.610.270.150.550.250.14      
VzH=3.2      0.40.210.130.310.160.10.280.150.09      
 H=3.8      0.210.130.090.160.10.070.150.090.06      
Vk  31.91.2  
X0,25  2.42.22.1  
Ps  37135  
Lw(A)  4325<20  
200 H=2.7         0.810.360.20.730.330.180.530.230.12   
VzH=3.2         0.40.220.130.370.20.120.260.140.08   
 H=3.8         0.220.130.090.20.120.080.140.080.05   
Vk   2.51.61 
X0,25   2.42.42 
Ps   2393 
Lw(A)   3321<20 
250 H=2.7         10.450.240.920.410.230.690.30.160.390.150.08
VzH=3.2         0.50.270.160.460.250.150.340.180.110.180.080.05
 H=3.8         0.270.160.110.250.150.10.180.110.070.080.050.03
Vk   3.121.31
X0,25   2.72.62.31.8
Ps   351455
Lw(A)   4027<20<20
300 H=2.7            1.10.490.270.850.370.20.470.180.09
VzH=3.2            0.550.30.180.420.220.130.210.10.06
 H=3.8            0.30.180.120.220.130.090.10.060.04
Vk    2.41.61.2
X0,25    2.82.51.9
Ps    2087
Lw(A)    32<20<20
350 H=2.7            1.280.570.320.960.420.220.550.220.11
VzH=3.2            0.650.350.210.470.250.150.250.120.07
 H=3.8            0.350.210.140.250.150.10.120.070.04
Vk    2.81.81.4
X0,25    32.62
Ps    271010
Lw(A)    3722<20
400 H=2.7            1.470.660.361.110.490.260.630.250.12
VzH=3.2            0.740.390.240.550.290.170.280.140.08
 H=3.8            0.390.240.160.290.170.110.140.080.05
Vk    3.22.11.6
X0,25    3.12.82.1
Ps    351412
Lw(A)    412724
500 H=2.7               1.380.60.320.830.320.16
VzH=3.2               0.680.360.210.370.180.1
 H=3.8               0.360.210.140.180.10.06
Vk     2.62.1
X0,25     32.3
Ps     2121
Lw(A)     3534

Symbols and specifications

  • Q = Air volume in m³/h
  • Ak = Effective surface (free area) in m²
  • B = Distance between the diffusers in m
  • H = Installation height of the diffusers in m
  • Vz = Maximum velocity at the occupied zone according to distance between the diffusers and installation height in m/s
  • Vk = Average effective velocity through the diffuser in m/s
  • X0.25 = Throw length in m at an end velocity Vt of 0,25m/s
  • Ps = Static pressure loss given in Pa
  • Lw(A) = Acoustic power in dB(A)


  • The throw X0.25 is given at an end velocity of 0.25m/s for a smooth ceiling without any obstacles.
  • The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by dividing the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.
  • In order to achieve a high comfort level, selections can be made according to the maximal velocity at the occupied zone Vz. These values are given at distances between diffusers B and installation heights H. Velocities Vz lower than, or equal to 0,25m/s at the occupied zone are advised.
  • The pressure losses Ps are given for diffusers without damper of with fully opened damper.
  • The acoustic power values Lw(A) are given for diffusers without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
  • For all special requirements, please contact our engineering office.