ПРОДУКТИ
Код за електронния магазин
Парола
Welcome to Cairox Bulgaria

ASM • Linear slot diffusers

  • Slot diffusers
  • Linear
  • Aluminium
  • Anodized natural finish

Linear slot diffusers without adjustable deflector or volume control damper

Application

  • For supply or exhaust in ventilation and air conditioning systems.

Material

  • Aluminium

Colour

  • Anodized aluminium, natural finish

Mounting

  • Ceiling- or wall mounted

Accessories

  • Non-insulated plenum box Type PR
  • 2-sides insulated plenum box Type PRI. 5-sides insulated on request
  • Corner piece 90° ASM K90
  • Connection piece ASM-CON

Text for tender

Копирай
  • The air diffusers are of the linear type without deflector or damper. They are made of aluminium natural finish and supplied with a non-insulated plenum box.
  • ATC
  • Type ASM + PR

Order example

  • ASM 2, 1500 + PR 2 1500 + ASM-CON

Explanation

ASM = Diffuser type

2 = Slot quantity

1500 = Length of diffuser

Accessories (optional)

PR 2 1500 = Not-insulated plenum box for diffuser of 2 slots with a length of 1500mm

ASM-CON = Connection piece to mount several diffusers in line

Dimensions

SABFGHD
[mm][mm][mm][mm][mm][mm]
175637666223125
21119994102274160
3147135114138325200
4183171114174376200
5219207114210376200
6255243114246376200

Notes

  • S = number of slots

Selection

Тип600-1900-11200-11500-1900-21200-2900-31500-21200-31500-31200-41500-4
600-2 600-3600-4 900-4
Светло сечение0.0060.0090.0120.0150.0180.0240.0270.0300.0360.0450.0480.060

[m2]

Дебит [m3/h]

602.81.51.91.21.41.11.11.0
19.027.08.0<205.0<203.0<20
803.7202.51.71.91.41.51.31.21.2
35.035.014.027.09.021.06.0<205.0<20
1004.62.53.12.12.31.81.91.61.51.51.21.31.01.2
54.041.021.033.014.027.09.023.08.0<205.0<204.0<20
1406.53.54.32.93.32.52.62.22.22.01.61.81.41.71.31.61.11.4
10651.041.042.028.037.018.032.015.029.011.023.08.021.04.0<204.0<20
180 5.63.74.23.23.32.92.82.62.12.31.92.11.72.01.41.91.11.71.01.6
68.049.046.044.030.039.024.036.018.030.013.027.07.025.07.024.05.0<204.0<20
200 6.24.14.63.63.73.23.12.92.32.52.12.41.92.31.52.11.21.81.21.8
84.052.057.047.036.042.030.028.022.033.016.030.09.028.08.027.06.022.05.021.0
250 5.84.54.64.03.93.62.93.22.63.02.32.81.92.61.52.31.52.21.22.0
89.053.057.048.047.045.034.039.024.037.014.034.013.033.09.028.08.027.05.023.0
300 5.64.84.64.43.53.83.13.62.83.42.33.11.92.81.72.71.42.4
     82.053.068.050.049.044.035.042.020.040.019.038.013.033.011.032.07.028.0
400 Метод на селекция 4.65.14.14.83.74.53.14.12.53.72.33.61.93.2
Всяка кутия съдържа 4 вида данни: 87.052.062.050.035.047.034.046.023.041.020.040.013.036.0
500 4.65.63.95.23.14.62.94.52.34.0

Veff

11.213.1Lt  55.054.053.052.036.048.032.046.020.042.0
600 Pa50.048.0Lw  3.75.53.55.42.84.8
  52.053.045.051.029.047.0
700

Veff = ефективна скорост в m/s

4.16.33.35.6
Lt = далекобойност при ск-ст Vt 0.25 m/s 62.056.040.051.0
800 Pa = загуба на налягане 3.76.4
Lw = шумово ниво (dB(A)) 52.055.0

Symbols and specifications

  • Values at ceiling height of 2.7m
  • Temperature difference Dt = -10K
  • Lth = Horizontal throw in m at vr = 0.15m/s
  • Ltv = Vertical throw in m at vr = 0.15m/s
  • Ps = Static pressure loss in Pa
  • Lp = Acoustic pressure incl. 5dB of room attenuation in dB(A)
  • Qv = Air Volume in m³/h
  • Horizontal or vertical supply
CopyrightEthics policyDisclaimerDuct calculator

Търсене на информация. Моля, изчакайте ..