Scatters of type Diffuser line are designed to mix the air wherever there is the need to eliminate heat and humidity stratification, with consequent wastes of energy and discomfort for the people. For instance in industrial and commercial buildings, sporting halls, warehouses, stores, stock-farms etc.
Advantages
Diffuser provides the mixing of the air, even in big size environments, allowing a uniform temperature in any point and height. It is known that during the winter season, the hot air has the tendency to rise up to the top dispersing through the roof covering and windows
An industrial environment heated with thermal appliances could have up to 15°C difference in temperature between the floor and the ceiling. A great amount of energy is therefore wasted to guarantee a satisfactory temperature to the ground. During the summer season there is a stratification of the dumpy air towards the ground, therefore the mixing of this air, together with the opening of the windows, consent the renewal improving the living conditions
Composition
Ring casing, with double wide round shaped nozzles, and diffuser resistant to atmospheric agents
Chains and fixing bracket
Inlet grid in steel rod, protected against the atmospheric agents
Impeller with high efficiency air foil blades in plastic materials and hub in die-cast aluminum. Balancing according to UNI ISO 1940
Asynchronous electric motor three and single phase with thermal protection, speed adjustable, protection IP 55, Class F insulated, service S1
Impeller directly coupled to motor shaft
Temperature of conveyed air: -20°C / +50°C
Supply:
1ph 230V 50 Hz (80 M) speed adjustable
3ph 400V 50 Hz (80 T)
Air flow from motor to impeller
Options
Standard version suitable for working temperature: -25°C / +50°C
ATEX94/9/CE flameproof version
Text for tender
Axial scatter fans for mixing of the air, allowing a uniform temperature in any point and height
ATC type Diffuser
Axial scatter fans for mixing of the air, allowing a uniform temperature in any point and height
ATC type Diffuser
Order example
Diffuser 80 T
Explanation:
Diffuser - type fan
T - 3-phase (M - 1-phase)
Qv
RPM
P
I
[m3/h]
[min-1]
[kW]
[A]
80 M
9000
450
0.14
2.3
80 T
10500
530
0.12
0.7
Sound levels
80 М
80 T
RPM
Lp
RPM
Lp
[min-1]
[dB(A)]
[min-1]
[dB(A)]
450
54
530
59
310
46
400
51
220
40
260
43
Notes
Lp = Sound level
Mounting
Mounting
The
ideal installation consists to place one Diffuser each 200-250 m2
covering all the flooring, paying attention not to overlap the
ventilation areas and keeping distance from perimeter walls, so to avoid
troublesome vertical airflow currents. Maximum height of installation:
6-7 meters from the ground. We suggest to install the Diffuser with an
automatic regulation panel, or in alternative with a speed regulator
with (or without) thermostat and feeler. We also recommend setting
thermostat with a temperature not lower than 20°C, to avoid the movement of “cold” air.
Working principles
Notes
** - Air temperature in operation (and stopped) conditions