PRODUCTS
EShop-number
Password
Welcome to Cairox Bulgaria

RIS P • Air handling units

  • Heat recovery units
  • Counter flow
  • 420 ≤ Qv ≤ 2500 m³/h

Application

  • Ventilation of houses, offices or other heated premises (classrooms, apartments, conference rooms, etc.)

Composition

  • Frameless construction from double-skinned panels
  • Acoustic and thermal wall insulation: RIS 400–2500 P EKO 3.0 – 30/50 mm
  • RIS 400-700 P EKO 3.0 powder-coated white housing RAL 9016; RIS 1200–2500 P EKO 3.0 powder-coated grey housing RAL 7040
  • Integrated electrical heater or optional duct-based water heater/cooler
  • Low-pressure-drop filters: F7/M5
  • Hinged door with locks grants easy access to internal components
  • Separate compartment on the side of the unit grants quick access to the control board (plug-and-play)
  • Stainless steel condensate tray
  • Fitted with mounting brackets
  • Integrated anti-frost pressure switch (RIS 1200-2500 P EKO 3.0)

Characteristics

  • RIS P EKO 3.0 is a range of heat recovery units with high-efficiency counter-flow heat exchangers and low height. The units are designed for mounting under ceilings in order to save space. There are 5 sizes (airflow interval 420-2500 m3/h) with separate heaters available for different climate zones
  • RIS P EKO 3.0 units have high overall energy savings due to the highly efficient heat recovery (up to 90%), quiet and economical EC fans, effective low-pressure-drop filters, 100% motorized bypass dampers (for the 1900 and 2500 versions) and top-level of air tightness
  • Energy efficiency ensures full thermal comfort for passive houses, without an additional pre-heater at temperatures above -5°C
  • All the RIS P EKO 3.0 units are fully equipped with automatic controls. Optional external sensors for CO2 and humidity and the event planning feature will help to control automatically your climate (demand-level control)
  • RIS P EKO 3.0 units are service-friendly and are easy to mount. Filter pollution may be identified by timers or contamination controls (RIS 1200-2500 P EKO 3.0)
  • All units are supplied tested and ready to install
  • Three types of remote controllers: Flex, Stouch or Ptouch controllers; BMS connections; via PC MB-Gateway

Technical data

RIS PE EKO 3.0(400) 0.9(400) 1.6(400) 3.0(700) 1.2(700) 3.0(700) 4.5(1200) 3.0(1200) 6.0(1200) 9.0(1900) 3.0(1900) 6.0(1900) 12.0(2500) 4.5(2500) 9.0(2500) 18.0
Electrical heaterPhase / voltage50Hz / V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V~3Ph / 400V~1Ph / 230V~3Ph / 400V~3Ph / 400V~1Ph / 230V~3Ph / 400V~3Ph / 400V~3Ph / 400V~3Ph / 400V~3Ph / 400V
PowerkW0.91.63.01.23.04.53.06.09.03.06.012.04.59.018.
EC FansPhase / voltage50Hz / V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V
Exhaust fans power / curentkW / A0.085 / 0.730.085 / 0.730.085 / 0.730.168 / 1.40.168 / 1.40.168 / 1.40.450 / 2.950.450 / 2.950.450 / 2.950.485 / 3.120.485 / 3.120.485 / 3.120.725 / 3.240.725 / 3.240.725 / 3.24
Exhaust fans speedmin-1320032003200323032303230340034003400254025402540280028002800
Supply fans power / curentkW / A0.085 / 0.730.085 / 0.730.085 / 0.730.168 / 1.40.168 / 1.40.168 / 1.40.370 / 2.50.370 / 2.50.370 / 2.50.488 / 3.160.488 / 3.160.488 / 3.160.675 / 30.675 / 30.675 / 3
Supply fans speedmin-1320032003200323032303230340034003400254025402540280028002800
Thermal efficiency up to: *%909090909090909090909090909090
Motorized by-pass
Max. power consumptionkW / A1.07 / 5.51.77 / 8.53.17 / 14.51.54 / 8.343.34 / 15.844.84 / 9.33.82 / 18.496.82 / 14.199.82 / 18.493.97 / 20.326.97 / 14.9212.97 / 24.325.90 / 12.7810.40 / 19.2819.40 / 32.28
Control boardPRV V2PRV V2PRV V2PRV V2PRV V2PRV V2PRV V2PRV V2PRV V2PRV V2PRV V2PRV V2PRV V2PRV V2PRV V2
Filter classExhaust / supplyM5 / F7M5 / F7M5 / F7M5 / F7M5 / F7M5 / F7M5 / F7M5 / F7M5 / F7M5 / F7M5 / F7M5 / F7M5 / F7M5 / F7M5 / F7
Housing insulation, mineral woolmm303030303030505050505050505050
Colour / RALwhite / 9016white / 9016white / 9016white / 9016white / 9016white / 9016grey / 7040grey / 7040grey / 7040grey / 7040grey / 7040grey / 7040grey / 7040grey / 7040grey / 7040
Net weightkg747474103.5104104.5170170170269270272322322322
Comply with ERP2016; 20182016; 20182016; 20182016; 20182016; 20182016; 20182016; 20182016; 20182016; 20182016; 20182016; 20182016; 20182016; 20182016; 20182016; 2018
Operationindoorsindoorsindoorsindoorsindoorsindoorsindoorsindoorsindoorsindoorsindoorsindoorsindoorsindoorsindoors
Fresh air temperature limits: **°C-5 ~ +40-5 ~ +40-5 ~ +40-5 ~ +40-5 ~ +40-5 ~ +40-5 ~ +40-5 ~ +40-5 ~ +40-5 ~ +40-5 ~ +40-5 ~ +40-5 ~ +40-5 ~ +40-5 ~ +40
Housing protection classIP343434343434343434343434343434

Technical data

RIS PW EKO 3.0400700120019002500
Water heater (optional)AVS 200AVS 250SVS 500x250SVS 700x400SVS 700x400
FansVoltage50Hz / V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V~1Ph / 230V
Exhaust fans power / currentkW / A0.085 / 0.730.168 / 1.40.450 / 2.950.485 / 3.120.725 / 3.24
Exhaust fans speedmin-132003230340025402800
Supply fans power / currentkW / A0.085 / 0.730.168 / 1.40.370 / 2.50.488 / 3.160.675 / 3.0
Supply fans speedmin-132003230340025402800
Thermal efficiency up to: *%9090909090
Motorized by-pass
Max. power consumptionkW / A0.17 / 1.500.34 / 2.840.82 / 5.490.97 / 6.321.40 / 6.28
Control boardPRV V2PRV V2PRV V2PRV V2PRV V2
Filter classExhaust / supplyM5 / F7M5 / F7M5 / F7M5 / F7M5 / F7
Housing insulation, mineral woolmm3030505050
Colour / RALwhite / 9016white / 9016grey / 7040grey / 7040grey / 7040
Net weightkg73103170269322
Comply with ERP2016; 20182016; 20182016; 20182016; 20182016; 2018
Operationindoorsindoorsindoorsindoorsindoors
Fresh air temperature limits: **°C-5 ~ +40-5 ~ +40-5 ~ +40-5 ~ +40-5 ~ +40
Housing protection classIP3434343434

  • * Calculated according EN 13141-7.
  • ** For temperatures lower than recommended, use electrical pre-heater to ensure balanced operation

Dimensions

Dimensions

ModelWW1W2HH1H2H3H4FØDGD
[mm][mm][mm][mm][mm][mm][mm][mm][mm][mm][mm][mm]
RIS 400PE/PW EKO 3.0130013616507686701583309831200--
RIS 700PE/PW EKO 3.01380146169510699701603509940250--
RIS 1200PE/PW EKO 3.0155016557801497139717239010052-500250
RIS 1900PE/PW EKO 3.0175018707101955185019439910560-700300
RIS 2500PE/PW EKO 3.0185019707202055195024449910560-700400

Supply air

Exhaust air

Heat recovery performance

Configuration

Notes

  • IV - exhaust air fan
  • PV - supply air fan
  • PR - plate heat exchanger
  • PF - filter for supply air (class F7)
  • IF - filter for extract air (class M5)
  • M1 - actuator of by-pass damper
  • M4 - water heater circulation pump
  • M6 - optionally supplied mixing valve and motor
  • AVA - optionally supplied water cooler
  • AVS - optionally supplied water heater
  • SVS - optionally supplied water heater
  • T1 - antifrost thermostat
  • TL - fresh air temperature sensor
  • TJ - supply air temperature sensor
  • TE - exhaust air temperature sensor
  • TV - antifrost sensor
  • DTJ 100.1 - humidity + temperature sensor
  • EKA NV PH - optional fresh air pre-heater
  • EKS NV PH - optional fresh air pre-heater
  • PS1 - supply air differential pressure switch
  • PS2 - extract air differential pressure switch
  • PS3 - heat exchanger antifrost pressure switch