Multiple operation protection. Alternative cycle duty/defrosting operation. Anti-corrosion protection
- DC Inverter
High efficiency for energy saving. Quick start-up and less frequent start/stop - Environment friendly
R290 refrigerant, low GWP(GWP=3). Less carbon emission - Comfort
Multiple silence modes - EVI technology
Adopt EVI technology, the operation ambient temperature can reach at -25 ºC
Technical data
|
Heating
(A7/6℃,W30/35℃) | Heating Capacity | kW | 17.56~50.00 | 20.24~89.93 | | Power Input | kW | 2.61~12.88 | 3.65~21.50 | | Current Input | A | 5.46~18.80 | 5.55~32.67 | | COP | W/W | 6.72~3.88 | 4.18~5.55 | Heating
(A7/6℃,W47/55℃) | Heating Capacity | kW | 17.95~49.00 | 19.67~91.59 | | Power Input | kW | 3.48~17.20 | 5.65~29.36 | | Current Input | A | 7.78~26.80 | 8.58~44.61 | | COP | W/W | 5.16~2.85 | 3.08~3.44 | Cooling
(A35/24℃,W12/7℃) | Cooling Capacity | kW | 10.00~35.00 | 11.14~64.45 | | Power Input | kW | 3.84~14.50 | 3.04~21.98 | | Current Input | A | 6.42~20.56 | 4.62~33.40 | | EER | W/W | 2.60~2.41 | 2.93~3.66 | | ERP Level(35℃) | / | A++ | A+++ | | Rated water flow | m3/h | 8.60 | 12.9 | | Rated voltage /Frequency | V/Hz | 400V/3N~50hz | 380~415V/3N~50hz | | Maximum input power | kW | 19.84 | 45.84 | | Maximum input current | A | 30.30 | 70.6 | | Sound pressure at 1m distance | dB(A) | 65 | 65 | | Max outlet water temperature | °C | 75 | 75 | | Water piping connections | / | DN 40 (G 1-1/2") | DN65 | | Water Pressure drop(max) | kPa | 65 | 23 | | Min/Max Water Pressure | MPa | 0.1/0.3 | 0.1/0.3 | | Operating temperature range (Heating/Cooing) | °C | -25~45 / 16~45 | -25~45 / 16~45 | | Dimensions ( L×D×H ) | mm | 1155*990*1880 | 2200*1100*2180 | | Net Weight | kg | 500 | 770 |
Dimensions
|
| Unpacked Dimensions ( L×D×H ) | mm | 1155x990x1880 | 2200x1100x2180 | | Net Weight | kg | 500 | 770 |
|