PRODUCTS
EShop-number
Password
Welcome to Cairox Bulgaria

CHP R-AQUA 2 290 • Heatpump R290

  • R-AQUA
  • Heatpump inverter
  • Monoblock

  • R290 Air source heat pump 50 kW R290

Application

  • Hot water
  • Heating
  • Cooling

Brand

  • ATC / Gree

Refrigerant

  • R290

Specifications

  • High reliability
Multiple operation protection. Alternative cycle duty/defrosting operation. Anti-corrosion protection
  • DC Inverter
    High efficiency for energy saving. Quick start-up and less frequent start/stop
  • Environment friendly
    R290 refrigerant, low GWP(GWP=3). Less carbon emission
  • Comfort
    Multiple silence modes
  • EVI technology
    Adopt EVI technology, the operation ambient temperature can reach at -25 ºC

Technical data

Model: CHP-050TC3CHP-075TC3
Heating
(A7/6℃,W30/35℃)
Heating CapacitykW17.56~50.0020.24~89.93
Power InputkW2.61~12.883.65~21.50
Current InputA5.46~18.805.55~32.67
COPW/W6.72~3.884.18~5.55
Heating
(A7/6℃,W47/55℃)
Heating CapacitykW17.95~49.0019.67~91.59
Power InputkW3.48~17.205.65~29.36
Current InputA7.78~26.808.58~44.61
COPW/W5.16~2.853.08~3.44
Cooling
(A35/24℃,W12/7℃)
Cooling CapacitykW10.00~35.0011.14~64.45
Power InputkW3.84~14.503.04~21.98
Current InputA6.42~20.564.62~33.40
EERW/W2.60~2.412.93~3.66
ERP Level(35℃)/A++A+++
Rated water flowm3/h8.6012.9
Rated voltage /FrequencyV/Hz400V/3N~50hz380~415V/3N~50hz
Maximum input powerkW19.8445.84
Maximum input currentA30.3070.6
Sound pressure at 1m distancedB(A)6565
Max outlet water temperature°C7575
Water piping connections/DN 40 (G 1-1/2")DN65
Water Pressure drop(max)kPa6523
Min/Max Water PressureMPa0.1/0.30.1/0.3
Operating temperature range (Heating/Cooing)°C-25~45 / 16~45-25~45 / 16~45
Dimensions ( L×D×H )mm1155*990*18802200*1100*2180
Net Weightkg500770

Dimensions

Model CHP-050TC3CHP-075TC3
Unpacked Dimensions ( L×D×H )mm1155x990x18802200x1100x2180
Net Weightkg500770

CopyrightEthics policyDisclaimerDuct calculator

Requesting information. Please wait a moment...