ПРОДУКТИ
Код за електронния магазин
Парола
Welcome to Cairox Bulgaria

BLM-F • Spring return actuators

  • Aeraulic
  • Actuators
  • With spring return

Technical data

TF ..LF ..NF .. ASF .. AEF .. A
2 Nm4 Nm10 Nm

20 Nm

30 Nm
For air dumper sizes up to aprrox.

0.4 m2

0.8 m2

2 m2

4 m2

6 m2

Open-close actuators
AC/DC 24V TF24LF24NF24ASF24AEF24A
with auxiliary switch, 1 x SPDTTF24-SLF24-S---
with auxiliary switch, 2 x SPDT--NF24A-S2SF24A-S2EF24A-S2
AC 230V TF230LF230NF230ASF230AEF230A
with auxiliary switch, 1 x SPDTTF230-SLF230-S---
with auxiliary switch, 2 x SPDT--NF230A-S2SF230A-S2EF230A-S2

AC 24 ... 240V / DC 24 ... 125V

--NFASFA-
with auxiliary switch, 2 x SPDT--NFA-S2SFA-S2-
3-point actuator
AC 24VTF24-3-NF24A-3SF24A-3-
Modulating actuators

Control signal Y: DC 0 ... 10 V, 100 kΩ / Position feedback DC 2 ... 10 V or DC 0 ... 10 V, max. 1 mA

AC/DC 24V

Operating range DC 2 ... 10 V

TF24-SRLF24-SRNF24A-SRSF24A-SREF24A-SR

with auxiliary switch, 2 x SPDT

--NF24A-SR-S2SF24A-SR-S2EF24A-SR-S2

Operating range DC 0 ... 10 V

--NF24A-SZSF24A-SZ-

with auxiliary switch, 2 x SPDT

--NF24A-SZ-S2SF24A-SZ-S2-
AC 230V

Operating range DC 2 ... 10 V

TF230-SR----
Parametеrisable actuators

parametеrisable

AC/DC 24VTF24-MFTLFT24-MFTNF24A-MFSF24A-MFEF24A-MF
Technical data
Damper spindlediagonal / diameter

6 ... 12 mm

8 ... 16 mm

10 ... 25.4 mm

12 ... 25.4 mm

12 ... 26.7 mm

Running timeMotor< 75 s / 90°

< 40 ... 75 s / 90°

< 75 s / 90°

< 75 s / 90°< 75 s / 90°
SR: 150 s / 90°SR: 150 s / 90°SR/SZ: 150 s / 90°SR/SZ: 150 s / 90°SR/SZ: 150 s / 90°
Emergency control function< 25 s / 90°~ 20 s / 90°< 20 s / 90°< 20 s / 90°< 20 s / 90°
Manual override Hand crank
ConnectionCable 1 m / PVCCable FRNC 1 m
Direction of rotationCan be selected by mounting L / R
Angle of rotationMax. 95°, can be limited at both ends with adjustable mechanical end stops
Position indicationMechanical, pluggable
Sound power levelMotor

≤ 50 dB(A) - 75 s

≤ 50 dB(A) - 75 s

≤ 45 dB(A) - 75 s

≤ 50 dB(A) - 75 s

Emergency control function= 62 dB(A) - 25 s= 62 dB(A) - 20 s= 62 dB(A) - 20 s= 62 dB(A) - 20 s
Degree of protectionIP 42IP 54

IP 54 1)

EMCCE according to 2004/108/EC
Ambient temperature

-30 ... +50°C

Non-operating temperature

-40 ... +80°C

Ambient humidity95% r.h., non-condensating

Notes

1) EF..: IP 66 versions on request

CopyrightEthics policyDisclaimerDuct calculator

Търсене на информация. Моля, изчакайте ..