PRODUCTS
EShop-number
Password
Welcome to Cairox Bulgaria

MVC • Actuator for globe valves

  • Actuators

Compact actuator for globe valves

Application

MVC actuator can be used with valves push/pull (using auto stroke calibration) or with valves with spring return using fixed stroke to
control hot/cool water flow rate in two/four pipes terminal units, zone and solar plants, small reheating and dehumidification coils.

Specifications

MVC is an electrical bidirectional actuator. The valve stem is activated through a synchronous motor and a gear train optimised in
order to have high performances and minimal noise ejections. The actuator is equipped with a movement of limit force which is able
to stop the power supply when the force of 300N is reached. If configured as auto calibration stroke, the software of the proportional
models enables the stroke calibration, so it can be used on any valve, as long as it respects the maximum stroke limit allowed (look
at the above table).

Technical data

CharacteristicMVC203MVC403MVC503
Power supply230 Vac ±10%24 Vac ± 10%
Consumption16,2 VA -1,1 W2,2 VA - 2,2 W3,6 VA - 3 W
Frequency50/60 Hz
Stroke timing (50 Hz)60 s : V.XT, VSB.T/VMB.T, VSBT./VMBT. 5,5 mm stroke
100 s : 2TGA.B 8,5 mm stroke
130 s : 2-3TGB.B 11,5 mm stroke
Speed11,5 s/mm at 50 Hz - 9,4 s/mm at 60 Hz
Force300 N (UNI 9497: 1989)
Operation temperature -5T55 °C
Storage temperature -25T65 °C
Protection classII (IEC 60950-1: 2005)
Connection cable3 wire 1,5 m5 wire 1,5 m (CEI 20-22/II)
Protection degreeIP54 (CEI EN 60529: 1997)
Weight0,25 Kg
Feedback signal 2-10 V (2 V fully retracted in direct
action or 2V fully extended
in reverse action)
Manual override Operable with 3 mm hex key
Referance Directives and Standards EMC 2014/30/UE according to EN 61326-1: 2013. LVD 2014/35/UE according to EN 61010-1: 2010
for MVC2xx.

Models

MODELCONTROL SIGNALPOWER SUPPLY MAX. STROKE
MVC2033-Point ON/OFF230 Vac16 mm
MVC40324 Vac
MVC503Proportional

Wiring Diagrams

Dimensions

CopyrightEthics policyDisclaimerDuct calculator